Printer Friendly Version of this Document

APPENDIX B

Fume System Logbook - Example

(Inside front cover, or attached to fume cupboard)

Laboratory: 123 (Crystal Chemistry)
Laboratory Supervisor: Dr J Smith, x51234, Office: Rm 126
Fume cupboard number: 8135
Scrubbed cupboard:  

 

Operating guide -

pH range 6.5 – 9

Dosing chemical – Sodium hydroxide pellets  (10g / Tank)

pH to be checked fortnightly, under current usage

Consult the procedure attached to the inside of the back cover.

(page in book or loose leaf sheets in a folder)

Date Name

Maintenance Or Repair Conducted

Comment Operation Satisfactory?
1/5/95 Joe Bloggs Replaced light bulbs   Yes
3/5/95 Jane Smith Scrubber pH checked OK Yes
20/5/95 J Smith Scrubber pH checked pH=5, added NaOH Yes
5/6/95 Rob jones Scrubber pH checked OK Yes

Main user is now PhD student Fred Citizen x7862

12/6/95 J Smith   Acid usage increased,
Check scrubber pH weekly
 
19/6/95 F Citizen Scrubber pH checked OK  
22/6/95 J Waterman Airflow test and smoke test Passed Yes
26/6/95 F Citizen Scrubber checked pH OK, pipe leaking No
27/6/95 John Piper  Scrubber leak fix Job number 95101 Yes